A Modbus read response contains the returned values, but not the starting register address. To interpret it correctly, identify the transport and function, check frame integrity, then use the original request and device register map to assign addresses and data types.

1. Decode an RTU FC03 response

Open the online Modbus frame parser, select Modbus RTU and Response, and load the example. Use start address 0 for this demonstration.

01 03 04 00 64 00 C8 BA 7A
RTU sample, grouped by field
BytesFieldMeaning
01Unit addressDevice 1
03FunctionRead holding registers
04Byte count4 data bytes, or 2 registers
00 64First register100 as unsigned 16-bit AB
00 C8Second register200 as unsigned 16-bit AB
BA 7ACRC bytesCRC 0x7ABA, low byte first

Select Parse frame. The tool reports a valid CRC and two rows containing 100 and 200. With start address 0, the rows are labeled 0 and 1. These addresses come from your input, not the read-response bytes.

2. Read the equivalent TCP frame

Select Modbus TCP, Response and Load example. The TCP sample carries the same two register values:

00 01 00 00 00 07 01 03 04 00 64 00 C8

00 01 is the transaction ID and 00 00 is the protocol ID. The length field 00 07 counts seven following bytes, beginning with Unit ID 01. The PDU begins with function 03, followed by byte count 04 and the data. This frame has no RTU CRC trailer.

3. Confirm addresses and byte order

Modbus PDU addresses are zero-based. A device manual may instead use reference labels such as 40001. Check the manufacturer’s convention before entering an address. An FC03 response returns two bytes per register, high byte first. See the Modbus Application Protocol specification, section 6.3.

For values spanning two registers, use the parser’s Columns & byte order control to compare formats. Match the result to the device’s documented type, register order, scaling and expected range. A plausible-looking float by itself does not establish the correct format.

4. Investigate warnings before using a value

Save your findings or connect to the device

Add labels and annotations and export CSV before leaving the parser. Pasted frames remain in the browser; the online tool does not communicate with hardware. For live connections, scanning, monitoring and write tests, download the Windows desktop app.